TP100DRL DIN Rail Mount Power Supplies - Enclosed 100w 100 Watt

TP100DRL DIN Rail Mount Power Supplies – Enclosed 100w 100 Watt

100W Triple Output with PFC Function

  • Universal AC input/full range
  • Built-in active PFC function, PF>0.94
  • Protections: Short circuit/Over load/Over voltage
  • Free air cooling convection
  • Fixed switching frequency at 100KHz (Optional)



Model Number
Output Voltage
Output Amps
Voltage Tolerance
Minimum Load Requirement
Efficiency
TP100-A5V, 12V, -5V10A, 4A, 0.6A +/-3.0%,+/-7.0%, +/-6.0% (Note 3)3~15A, 0.4~5A, 0~1A75% typ.
TP100-B5V, 12V, -12V10A, 4A, 0.6A +/-3.0%,+/-6.0%, +/-6.0% (Note 3)3~15A, 0.4~5A, 0~1A78% typ.
TP100-C5V, 15V, -15V10A, 3A, 0.6A +/-3.0%,+10,-6.%, +/-6.0% (Note 3)3~15A, 0.4~4A, 0~1A77% typ.
TP100-D5V, 24V, 12V10A, 2A, 0.6A +/-3.0%,+/-8.0%, +/-6.0% (Note 3)3~15A, 0.4~3A, 0~1A78% typ.

TP100/DRL series

Input Specifications

Input Voltage Range 90-264VAC 127~370VDC (Note 5)
Frequency Range 47~63Hz
Inrush Current Cold Start ?40A/230V typ.
Input Current 1.5A/115VAC 0.75A/230VAC
Leakage Current <3.5mA/240VAC
Power Factor Correction PF>0.94/230VAC PF>0.98/115VAC at Full Load typ.

General Specifications

Isolation 3KVAC (Note 4)
Isolation Input-Ground 1.5KVAC (Note 4)
Isolation Output-Ground 0.5KVAC (Note 4)
Insulation Resistance 100M Ohms/500VDC (Note 4)
Efficiency 75% typ.
Safety Approvals UL60950-1, TUV EN60950-1 Approved (Note 4)
Harmonic Current Compliance to EN61000-3-2,-3 (Note 4)

Environmental Specifications

Operating Temperature -10~+60°C (Refer to output load derating curve)
Storage Temperature -20~+85°C
Working Humidity 20 ~ 90 % RH non-condensing
Storage Humidity 10~95% RH
EMI Compliance to EN55022 (CISPR22) Class B (Note 4)
MTBF 170.1K hrs. min MIL-HDBK-217F (25°C)
Vibration 10~500HZ, 2G 10 min/1 cycle, 60 min. each along X, Y, Z axes
EMS Compliance to EN-61000-4-2,3,4,5,6,8,11; ENV50204, EN55024, Light industry level, criteria A (Note 4)

Output Specifications

Output Voltage 5V
Output Amps 10A
Load Regulation ±3.0%
Line Regulation ±1%
Temperature Coefficient ±0.03%/°C (0~50°C)
Ripple and Noise 100mVp-p max. (Note 2)
Over Voltage Protection CH1: 5.75~6.75V on 5V. Protection type: Shut down o/p voltage, re-power on to recover
Over Current Protection 105~150% rated output power. Protection type: Hiccup mode, recovers automatically after fault condition is removed.
Over Temperature Protection 95°C ±5°C (TSW1). Protection type: shot down o/p voltage, recovers automatically after temperature goes down.
Voltage Tolerance ±3.0% (Note 3)
DC Voltage Adjust 4.75~5.5V
Minimum Load Requirement 3~15A
Rise Time 800ms, 60ms/230VAC; 800ms, 60ms/115VAC at full load
Hold Up Time 24ms/230VAC 24ms/115VAC at full load typ.

Physical Specifications

Size (mm) 199mm x 99mm x 50mm
Weight (g) 0.83Kg; 20pcs/17.6Kg/1.28CUFT

Notes

  1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 °C of ambient temperature.
  2. Ripple and noise are measured at 20MHz of bandwidth by using a 12” twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
  3. Tolerance: includes set up tolerance, line regulation and load regulation.
  4. The power supply is considered a component which will be installed into a final equipment. The final equpiment must be re-confirmed that it still meets EMC directives.
  5. Derating may be needed under low input voltages. Please check the derating curve for more details.

All specifications are typical at nominal input, full load, and 25°C unless otherwise noted

Astrodyne products are not authorized or warranteed for use as critical components in life support systems, equipment used in hazardous environments, nuclear controls systems, or other mission-critical applications.