Order by phone: 1-800-823-8082 / +1-508-964-6300 M-F 8:30am to 5:30pm EST

SP75DRL 75 Watt DIN Rail Mount Enclosed Power Supplies

75W Single Output with PFC Function

Universal AC input/full range

Built-in active PFC function, PF>0.93

Protections: Short circuit/Over Load/Over voltage

Built-in constant current limiting circuit

Low profile: 33mm thickness

LED indicator for power on

Model Number

Output Voltage

Output Amps

Load Regulation

Ripple and Noise

Over Voltage Protection

Voltage Tolerance

DC Voltage Adjust

Minimum Load Requirement

Efficiency

SP75-3.3 3.3V 15A

+/-1%

80mVp-p max. (Note 2)

3.8~4.46V Protection type: Shut down o/p voltage, re-power on the recover

+/-2.0% (Note 3)

3.14~3.63V

0~15A

68% typ.

SP75-5 5V 15A

+/-1%

80mVp-p max. (Note 2)

5.75~6.75V Protection type: Shut down o/p voltage, re-power on the recover

+/-2.0% (Note 3)

4.75~5.5V

0~15A

72% typ.

SP75-7.5 7.5V 10A

+/-1%

80mVp-p max. (Note 2)

8.63~10.13V Protection type: Shut down o/p voltage, re-power on the recover

+/-2.0% (Note 3)

7.13~8.25V

0~10A

74% typ.

SP75-12 12V 6.3A

+/-0.5%

80mVp-p max. (Note 2)

13.8~16.2V Protection type: Shut down o/p voltage, re-power on the recover

+/-2.0% (Note 3)

11.4~13.2V

0~6.3A

77% typ.

SP75-13.5 13.5V 5.6A

+/-0.5%

80mVp-p max. (Note 2)

15.53~18.23V Protection type: Shut down o/p voltage, re-power on the recover

+/-2.0% (Note 3)

12.8~14.9V

0~5.6A

78% typ.

SP75-15 15V 5A

+/-0.5%

80mVp-p max. (Note 2)

17.25~20.25V Protection type: Shut down o/p voltage, re-power on the recover

+/-2.0% (Note 3)

14.3~16.5V

0~5A

79% typ.

SP75-24 24V 3.2A

+/-0.5%

100mVp-p max. (Note 2)

27.6~32.4V Protection type: Shut down o/p voltage, re-power on the recover

+/-1.0% (Note 3)

22.8~26.4V

0~3.2A

80% typ.

SP75-27 27V 2.8A

+/-0.5%

100mVp-p max. (Note 2)

31.05~36.45V Protection type: Shut down o/p voltage, re-power on the recover

+/-1.0% (Note 3)

25.7~29.7V

0~2.8A

80% typ.

SP75-48 48V 1.6A

+/-0.5%

100mVp-p max. (Note 2)

55.2~64.8V Protection type: Shut down o/p voltage, re-power on the recover

+/-1.0% (Note 3)

45.6~52.8V

0~1.6A

80% typ.

SP75/DRL series

Input Specifications

General Specifications

Isolation

3KVAC (Note 4)

Isolation Input-Ground

1.5KVAC (Note 4)

Isolation Output-Ground

0.5KVAC (Note 4)

Insulation Resistance

100M Ohms/500VDC (Note 4)

Efficiency

68% typ.

Safety Approvals

UL60950-1, TUV EN60950-1 Approved

Harmonic Current

Compliance to EN61000-3-2,-3 (Note 4)

Environmental Specifications

Operating Temperature

-10~+60°C (Refer to output load derating curve)

Storage Temperature

-20~+85°C

Working Humidity

20 ~ 90 % RH non-condensing

Storage Humidity

10~95% RH

EMI

Compliance to EN55022 (CISPR22) Class B (Note 4)

MTBF

208.8K hrs min. MIL-HDBK-217F (25°C)

Vibration

10~500Hz, 2G 10min./1 cycle, 60 min. each along X, Y, Z axes

EMS

Compliance to EN6-1000-4-2,3,4,5,6,8,11; ENV50204, EN55024, Light industry level, criteria A (Note 4)

Input Voltage Range

85~264VAC 120~370VDC (Note 5)

Frequency Range

47~63Hz

Inrush Current

Cold Start 30A/230VAC typ.

Input Current

1.3A-115VAC 0.7A/230VAC typ.

Leakage Current

<2mA/240VAC

Power Factor Correction

PF>0.93/230VAC 0.96/115VAC at full load

Output Specifications

Output Voltage

3.3V

Output Amps

15A

Load Regulation

±1%

Line Regulation

±0.5%

Temperature Coefficient

±0.05%/°C (0~50°C)

Ripple and Noise

80mVp-p max. (Note 2)

Over Voltage Protection

3.8~4.46V Protection type: Shut down o/p voltage, re-power on the recover

Over Current Protection

105~150% rated output power. Protection type: Constant current limiting, recovers automatically after fault condition is removed

Voltage Tolerance

±2.0% (Note 3)

DC Voltage Adjust

3.14~3.63V

Minimum Load Requirement

0~15A

Rise Time

600ms, 60ms at full load

Hold Up Time

36ms at full load typ.

Remote Shutdown

CN3:4~10VDC POWER OFF, <0 ~ 0.8VDC POWER ON

Physical Specifications

Size (mm)

179mm x 97mm x 33mm

Weight (g)

0.58Kg; 20pcs/12Kg/0.64CUFT

Notes

1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 °C of ambient temperature.

2. Ripple and noise are measured at 20MHz of bandwidth by using a 12” twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.

3. Tolerance: includes set up tolerance, line regulation and load regulation.

4. The power supply is considered a component which will be installed into a final equipment. The final equpiment must be re-confirmed that it still meets EMC directives.

5. Derating may be needed under low input voltages. Please check the derating curve for more details.

All specifications are typical at nominal input, full load, and 25°C unless otherwise noted

Astrodyne products are not authorized or warranteed for use as critical components in life support systems, equipment used in hazardous environments, nuclear controls systems, or other mission-critical applications.