SD350 350 Watt Enclosed Converters
|
2:1 wide input range |
|
|
Protections: Short circuit/Over load/Over voltage/Over temperature |
|
|
1500VDC I/O isolation |
|
|
Forced air cooling by built-in DC fan |
|
|
100% full load burn-in test |
|
|
24V and 48V input voltage design refer to LVD |
|
Model Number |
Input Voltage Range |
DC Current |
Inrush Current |
Minimum Load Requirement |
Output Voltage |
Output Amps |
Line Regulation |
| SD350B-5 | 19~36VDC | 14.4A/24V typ. |
0~57A |
5V |
57A |
±0.5% |
|
| SD350B-12 | 36~72VDC | 16A/24V typ. |
0~27.5A |
12V |
27.5A |
±0.3% |
|
| SD350B-24 | 72~144VDC | 17.6/24V typ. |
0~14.6A |
24V |
14.6A |
±0.2% |
|
| SD350B-48 | 19~36VDC | 17.6A/24V typ. |
0~7.3A |
48V |
7.3A |
±0.2% |
|
| SD350C-5 | 36~72VDC | 7.6A/48V typ. |
45A/48VDC typ. |
0~60A |
5V |
60A |
±0.5% |
| SD350C-12 | 72~144VDC | 8.8A/48V typ. |
45A/48VDC typ. |
0~27.5A |
12V |
27.5A |
±0.3% |
| SD350C-24 | 19~36VDC | 8.6A/48V typ. |
45A/48VDC typ. |
0~14.6A |
24V |
14.6A |
±0.2% |
| SD350C-48 | 36~72VDC | 8.6A/48V typ. |
45A/48VDC typ. |
0~7.3A |
48V |
7.3A |
±0.2% |
| SD350D-5 | 72~144VDC | 4A/96V typ. |
45A/96VDC typ. |
0~60A |
5V |
60A |
±0.5% |
| SD350D-12 | 19~36VDC | 4.4A/96V typ. |
45A/96VDC typ. |
0~29.2A |
12V |
29.2A |
±0.3% |
| SD350D-24 | 36~72VDC | 4.2A/96V typ. |
45A/96VDC typ. |
0~14.6A |
24V |
14.6A |
±0.2% |
| SD350D-48 | 72~144VDC | 4.2A/96V typ. |
45A/96VDC typ. |
0~7.3A |
48V |
7.3A |
±0.2% |
|
Model Number |
Ripple and Noise |
Voltage Tolerance |
Over Voltage Protection |
DC Voltage Adjust (typ.) |
Efficiency |
|
SD350B-5 |
100mVp-p max. (Note 2) |
±2% (Note 3) |
5.75~6.75V Protection type: Shutdown o/p voltage, re-power on to recover |
4.5~5.5VDC |
74% typ. |
|
SD350B-12 |
120mVp-p max. (Note 2) |
±1% (Note 3) |
16.8~20V Protection type: Shutdown o/p voltage, re-power on to recover |
11~16VDC |
80% typ. |
|
SD350B-24 |
150mVp-p max. (Note 2) |
±1% (Note 3) |
31.5~37.5V Protection type: Shutdown o/p voltage, re-power on to recover |
23~30VDC |
80% typ. |
|
SD350B-48 |
200mVp-p max. (Note 2) |
±1% (Note 3) |
53~65V Protection type: Shutdown o/p voltage, re-power on to recover |
43~53VDC |
84% typ. |
|
SD350C-5 |
100mVp-p max. (Note 2) |
±2% (Note 3) |
5.75~6.75V Protection type: Shutdown o/p voltage, re-power on to recover |
4.5~5.5VDC |
76% typ. |
|
SD350C-12 |
120mVp-p max. (Note 2) |
±1% (Note 3) |
16.8~20V Protection type: Shutdown o/p voltage, re-power on to recover |
11~16VDC |
81% typ. |
|
SD350C-24 |
150mVp-p max. (Note 2) |
±1% (Note 3) |
31.5~37.5V Protection type: Shutdown o/p voltage, re-power on to recover |
23~30VDC |
81% typ. |
|
SD350C-48 |
200mVp-p max. (Note 2) |
±1% (Note 3) |
53~65V Protection type: Shutdown o/p voltage, re-power on to recover |
43~53VDC |
82% typ. |
|
SD350D-5 |
100mVp-p max. (Note 2) |
±2% (Note 3) |
5.75~6.75V Protection type: Shutdown o/p voltage, re-power on to recover |
4.5~5.5VDC |
78% typ. |
|
SD350D-12 |
120mVp-p max. (Note 2) |
±1% (Note 3) |
16.8~20V Protection type: Shutdown o/p voltage, re-power on to recover |
11~16VDC |
83% typ. |
|
SD350D-24 |
150mVp-p max. (Note 2) |
±1% (Note 3) |
31.5~37.5V Protection type: Shutdown o/p voltage, re-power on to recover |
23~30VDC |
87% typ. |
|
SD350D-48 |
200mVp-p max. (Note 2) |
±1% (Note 3) |
53~65V Protection type: Shutdown o/p voltage, re-power on to recover |
43~53VDC |
89% typ. |
SD350 series
|
Input Specifications
General Specifications
Physical Specifications
Notes 1. All parameters NOT specially mentioned are measured at 24, 48, 96VDC input, rated load and 25 °C of ambient temperature. 2. Ripple and noise are measured at 20MHz of bandwidth by using a 12” twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Tolerance: includes set up tolerance, line regulation and load regulation. 4. The power supply is considered a component which will be installed into a final equipment. The final equpiment must be re-confirmed that it still meets EMC directives. All specifications are typical at nominal input, full load, and 25°C unless otherwise noted Astrodyne products are not authorized or warranteed for use as critical components in life support systems, equipment used in hazardous environments, nuclear controls systems, or other mission-critical applications. |
Output Specifications
Environmental Specifications
|