Order by phone: 1-800-823-8082 / +1-508-964-6300 M-F 8:30am to 5:30pm EST

PMK225D 225 Watt DIN Rail Mount Switch Mode Power Supplies

225 Watt DIN Rail Mountable Switching Power Supply with PFC

225 Watts Output power

Single Outputs

Universal 90-264VAC Input

4242VDC Input to Output Isolation

Active Power Factor Correction

Model Number

Output Voltage

Output Amps

Ripple and Noise

Efficiency

PMK225S-5D

5 VDC

40

100mV pk-pk (Notes 1, 4)

75% FL. Nom I/P

PMK225S-12D

12 VDC

18.8

120mV pk-pk (Notes 1, 4)

82% FL. Nom I/P

PMK225S-15D

15 VDC

15

150mV pk-pk (Notes 1, 4)

83% FL. Nom I/P

PMK225S-24D

24 VDC

9.4

240mV pk-pk (Notes 1, 4)

84% FL. Nom I/P

PMK225S-36D

36 VDC

6.25

360mV pk-pk (Notes 1, 4)

84% FL. Nom I/P

PMK225S-48D

48 VDC

4.7

480mV pk-pk (Notes 1, 4)

84% FL. Nom I/P

PMK225D series

Input Specifications

Input Voltage Range

90-264 VAC (100-240VAC Nom.)

Frequency Range

47 ~ 63Hz

Inrush Current

30A @ 115VAC Cold Start, FL* 60A @ 230VAC Cold Start, FL* typ.

Input Current

3.8 Amps max., 90V I/P 1.3Amps max, 264V I/P

Leakage Current

<0.2mA, 240Vin, 50Hz

Power Factor Correction

0.95, min. Nom I/P, FL

General Specifications

Isolation

4242VDC (Note 2)

Isolation Input-Ground

2121VDC (Note 2)

Isolation Output-Ground

707VDC (Note 2)

Insulation Resistance

?20M?

Efficiency

75% FL. Nom I/P

Safety Approvals

UL/cUL60950-1, EN60950-1 (TUV), EN60601-1-2:2001 (CE), IEC60950-1 (CB)

Environmental Specifications

Operating Temperature

-20 to +70°C (See Derate Curve)

Storage Temperature

-25 to +85°C

Working Humidity

10% to +95%,

Storage Humidity

5-95%

EMI

EN55022 Class B

MTBF

100,000 Hrs, min Mil Std 217F, 25°C

Vibration

4G Peak, 50-500Hz, 3 Axes

EMS

Harmonics Class D, 61000-3-2 Fluctuations 61000-3-3 ESD 61000-4-2 RS 61000-4-3 EFT 61000-4-4 Surge 61000-4-5 CS 61000-4-6 DIPS 61000-4-11

Drop Test

70 CM

Output Specifications

Physical Specifications

Size (Inches)

3.86”W x 7”L x 1.57”H

Weight (g)

703g

Weight (oz)

1.55 lb,

Construction

Enclosed

Notes

1. All measurements should be made directly at the terminals of the power supply.

2. Isolation for up to 1 minute duration.

3. Preset Accuracy measured at nominal load, 120VAC input.

4. O/P Noise measured directly at the pins/terminals at nominal load, 0.1uF ceramic bypass and 47uF electrolytic, pk-pk @ 20MHz bandwidth.

All specifications are typical at nominal input, full load, and 25°C unless otherwise noted

Astrodyne products are not authorized or warranteed for use as critical components in life support systems, equipment used in hazardous environments, nuclear controls systems, or other mission-critical applications.

Output Voltage

5 VDC

Output Amps

40

Load Regulation

±1%, max. 10%-FL

Line Regulation

±1%, max. LL-HL

Ripple and Noise

100mV pk-pk (Notes 1, 4)

Over Voltage Protection

130% max. Auto Recovery

Over Current Protection

150% max. Auto Recovery

Short Circuit Protection

Auto Recover after fault condition is removed

Preset Accuracy

±1%, typ (2% 5 Vout) (Note 3)

Rise Time

<4S, <20mS, typ (Nom I/P, FL)

Hold Up Time

20mS, typ (Nom I/P, FL)

Over-Shoot

<10% of Nominal Output

Under-Shoot

<10% of Nominal Output

Remote Shutdown

Open Collector, Logic “1” = ON, “0” = Off. No Termination necessary to maintain constant “On” operation

Remote Sense

Compensates for up to 0.5V drop