Order by phone: 1-800-823-8082 / +1-508-964-6300 M-F 8:30am to 5:30pm EST

MDR60 60 Watt DIN Rail Mount Power Supplies

60W Single Ouput Industrial DIN Rail Power Supply

Universal AC input

Protections: Short circuit/Overload/ Over voltage

Cooling by free air convection

Can be installed on DIN rail S-35/7.5 or 15

NEC class 2/LPS compliant

LED indicator for power on, DC OK relaty contact, No load power consumption of <0.75W

Model Number

Output Voltage

Output Amps

Load Regulation

Ripple and Noise

Over Voltage Protection

Voltage Tolerance

DC Voltage Adjust

Minimum Load Requirement

Efficiency

MDR-60-5

5vdc

10 Amps

±1.5%

80mV pk-pk (Note 1)

6.25~7.25V Shutdown o/p voltage, re-power

±2% (Note 2)

5~6V

0 ~ 10Amps

78%

MDR-60-12

12vdc

5 Amps

±1%

120mV pk-pk (Note 1)

15.6~18V Shutdown o/p voltage, re-power

±1% (Note 2)

12~15V

0 ~ 5Amps

86%

MDR-60-24

24vdc

2.5 Amps

±1%

150mV pk-pk (Note 1)

31.2~36V Shutdown o/p voltage, re-power

±1% (Note 2)

24~30V

0 ~ 2.5Amps

88%

MDR-60-48

48vdc

1.25 Amps

±1%

200mV pk-pk (Note 1)

57.6~64.8V Shutdown o/p voltage, re-power

±1% (Note 2)

48~56V

0 ~ 1.25Amps

87%

MDR-60 series

Input Specifications

Input Voltage Range

90-264VAC / 120-370 Volts (DC)

Frequency Range

47 ~ 63Hz

Inrush Current

30 Amps @ 115VAC 60 Amps @ 230VAC (cold start) typ.

Input Current

1.8 Amps. @ 115VAC 1.0 Amps. @ 230VAC

Leakage Current

< 1mA / 240VAC

General Specifications

Isolation

3000VAC

Isolation Input-Ground

1500VAC

Isolation Output-Ground

500VAC

Insulation Resistance

? 100M? @ 500VDC

Efficiency

78%

Safety Approvals

UL508 TUV EN60950-1 Approved NEC class 2/LPS compliant (24V,48Vonly)

Harmonic Current

Compliance to EN61000-3-2,-3

Environmental Specifications

Operating Temperature

-20°C to +70°C (See Derate Curve)

Storage Temperature

-25 to +85°C

Working Humidity

20 to +90% RH, non cond

Storage Humidity

10 ~ 95% RH

EMI

Compliance to EN55022B (CISPR22B)

MTBF

299.2KHrs min, MIL-HDBK-217F(25°C)

Vibration

10~500Hz, 5G10min./1cycle, period for 60min. each along X, Y, Z axes

EMS

Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204, EN55024, EN60601-1-2, heavy industry level, criteria A

Output Specifications

Notes

Physical Specifications

Size (mm)

10 x 90 x 100

Size (Inches)

0.39” x 3.54 ” x 3.94 ”

Weight (g)

330g

Weight (oz)

11.64 oz

1. Ripple & Noise are measured at 20MHz of bandwidth by using a 12” twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.

2. Tolerance: includes set up tolerance , line regulation and load regulation.

All specifications are typical at nominal input, full load, and 25°C unless otherwise noted

Astrodyne products are not authorized or warranteed for use as critical components in life support systems, equipment used in hazardous environments, nuclear controls systems, or other mission-critical applications.

Output Voltage

5vdc

Output Amps

10 Amps

Load Regulation

±1.5%

Line Regulation

±1% max

Temperature Coefficient

± 0.03% / °C (0-50°C)

Ripple and Noise

80mV pk-pk (Note 1)

Over Voltage Protection

6.25~7.25V Shutdown o/p voltage, re-power

Over Current Protection

105~150% rated output power Constant current limiting,auto-recover

Voltage Tolerance

±2% (Note 2)

DC Voltage Adjust

5~6V

Minimum Load Requirement

0 ~ 10Amps

Rise Time

500ms, 30ms/230VAC 500mS, 30mS/115VAC @ FL

Hold Up Time

50mS @ 230VAC 20mS @115VAC @ FL