DRT240 240w Power Supplies

240W Three Phase Industrial DIN RAIL Power Supply

Three-Phase AC340 ~ 550V wide range input

High efficiency 89% and low dissipation

Protections; Short circuit / Over load/ Over voltage / Over temperature

Cooling by free air convection

Built-in constant current limiting circuit

Can be installed on DIN rail TS-35/7.5 or 15, UL 508(industrial control equipment) approved, EN61000-6-2(EN50082-2) industrial immunity level, 100% full load burn-in test

Model Number

Output Voltage

Output Amps

Over Voltage Protection

DC Voltage Adjust

Minimum Load Requirement

DRT-240-24

24V

10A

30~36V Shut down o/p voltage, re-power on to recover

24~48V

0~10A

DRT-240-48

48V

5A

59~66V Shut down o/p voltage, re-power on to recover

48~55V

0~5A

DRT-240 series

Input Specifications

Input Voltage Range

Three-Phase 340~550VAC 480~780VDC

Frequency Range

47 ~ 63Hz

Inrush Current

Cold start 50A (max)

Input Current

0.95A/400VAC 0.75A/500VAC

Leakage Current

<3.5mA / 530VAC

General Specifications

Isolation

3KVAC

Isolation Input-Ground

1.5KVAC

Isolation Output-Ground

0.5KVAC

Insulation Resistance

100M Ohms/500VDC

Efficiency

89% typ.

Safety Approvals

UL508, UL60950-1, TUV EN60950-1 Approved

Environmental Specifications

Operating Temperature

-20°C to +70°C (Refer to output load derating curve)

Storage Temperature

-40 ~ +85°C

Working Humidity

20~90% RH non condensing

Storage Humidity

10 ~ 95% RH

EMI

Compliance to EN55011 (CISPR11), EN55022(CISPR22), EN61204-3 Class B (Note 4)

MTBF

114.6Khrs min. MIL-HDBK-217F (25°C)

Vibration

10~500Hz, 2G 10min./1 cycle, 60 min each along x, y, z axes

EMS

Compiance to EN61000-4-2, 3, 4, 5, 6. 8, 11, ENV50204-3, EN61000-6-2 (EN50082-2) Heavy industry level, criteria A (Note 4)

Output Specifications

Output Voltage

24V

Output Amps

10A

Load Regulation

± 0.5%

Line Regulation

± 0.5%

Temperature Coefficient

± 0.03% / °C (0-50°C)

Ripple and Noise

80mVp-p max. (Note 2)

Over Voltage Protection

30~36V Shut down o/p voltage, re-power on to recover

Over Current Protection

105 ~ 150% rated output power Constant current limiting, recovers automatically after fault condition is removed

Over Temperature Protection

100°C ±5°C (TSW: Detect on heatsink of power switch) Shut down o/p voltage, recovers automatically after temperature goes down

Voltage Tolerance

± 1.0% (Note 3)

DC Voltage Adjust

24~48V

Minimum Load Requirement

0~10A

Rise Time

1200ms, 40ms/400VAC 800ms,40ms/500VAC at full load

Hold Up Time

20ms/400VAC 40ms/500VAC at full load

Physical Specifications

Size (mm)

125.5x125.2x100

Weight (g)

1.3Kg; 12pcs/16/6Kg/1/34CUFT

Notes

1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 °C of ambient temperature.

2. Ripple and noise are measured at 20MHz of bandwidth by using a 12” twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.

3. Tolerance: includes set up tolerance, line regulation and load regulation.

4. The power supply is considered a component which will be installed into a final equipment. The final equpiment must be re-confirmed that it still meets EMC directives.

5. Dual phase operation: derating of 20% is required.

All specifications are typical at nominal input, full load, and 25°C unless otherwise noted

Astrodyne products are not authorized or warranteed for use as critical components in life support systems, equipment used in hazardous environments, nuclear controls systems, or other mission-critical applications.