DRP480 480w Power Supplies

480W Single Output Industrial DIN RAIL with PFC Function

Built-in passive PFC function compliance to EN61000-3-2

Protections: Short circuit/over load /over voltage/over temperature

High efficiency 89% and low dissipation

Cooling by free air convection

Built-in constant current limiting circuit

Can be installed on DIN rail TS-35/7.5 or 15, UL 508(industrial control equipment) approved, EN61000-6-2(EN50082-2) industrial immunity level

Model Number

Input Voltage Range

Output Voltage

Output Amps

Over Voltage Protection

DC Voltage Adjust

DRP480-24

180-264VAC

24 Volts(DC)

0~20Amps

30~36 Volts(DC) Shut down o/p voltage, re-power

24~28Volts(DC)

DRP480S-24

90-132/180-264VAC

24 Volts(DC)

0~20Amps

30~36 Volts(DC) Shut down o/p voltage, re-power

24~28Volts(DC)

DRP480-48

180-264VAC

48 Volts(DC)

0~10Amps

54~60 Volts(DC) Shut down o/p voltage, re-power

48~53Volts(DC)

DRP480S-48

90-132/180-264VAC

48 Volts(DC)

0~10Amps

54~60 Volts(DC) Shut down o/p voltage, re-power

48~53Volts(DC)

DRP480 series

Input Specifications

Input Voltage Range

180~ 264VAC 250~370 Volts(DC)

Frequency Range

47 ~ 63Hz

Inrush Current

40 Amps / 230VAC (cold start) typ.

Input Current

4.0 Amps. @ 230VAC

Leakage Current

<3.5mA / 240 VAC

Power Factor Correction

PF ? 0.7

General Specifications

Isolation

3000VAC

Isolation Input-Ground

1500VAC

Isolation Output-Ground

500VAC

Insulation Resistance

? 100M? / 500Volts(DC)

Efficiency

89%

Safety Approvals

UL508, UL60950-1, TUV EN60950-1 Approved

Harmonic Current

Compliance to EN61000-3-2,-3

Environmental Specifications

Operating Temperature

-20°C to +70°C with cooling FAN

Storage Temperature

-40 ~ +85°C

Working Humidity

20~90% RH non condensing

Storage Humidity

10 ~ 90%RH

EMI

Compliance to EN55022B (CISPR22B)

MTBF

180.9KHrs min,MIL-HDBK-217F(25°C)

Vibration

10~500Hz, 2G10min./1cycle, period for 60min. each along X, Y, Z axes Mounting: Compliance to IEC60068-2-6

EMS

Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204, EN61000-6-2 (EN50082-2) light Industry Level, Criteria A

Output Specifications

Output Voltage

24 Volts(DC)

Output Amps

20 Amps

Load Regulation

± 1.0%

Line Regulation

±0.5%

Temperature Coefficient

± 0.03% / °C (0-50°C)

Ripple and Noise

120mVpk-pk (Note 1)

Over Voltage Protection

30~36 Volts(DC) Shut down o/p voltage, re-power

Over Current Protection

105 ~ 150% rated output power Constant current limiting,auto recover

Over Temperature Protection

100°C ±5°C (TSW: Detect on heatsink of power switch) Shut down o/p voltage,re-power after cool down

Voltage Tolerance

± 1.0% (Note 2)

DC Voltage Adjust

24~28Volts(DC)

Minimum Load Requirement

0~20Amps

Rise Time

1200ms, 40mS/230VAC @ FL

Hold Up Time

16mS/230VAC @ FL

Physical Specifications

Size (mm)

227 x 125.2 x 100

Size (Inches)

8.94” x 4.93 ” x 3.94 ”

Weight (g)

2400g

Weight (oz)

84.66 oz

Notes

1. Ripple & noise are measured at 20MHz of bandwidth by using a 12” twisted pair-wire terminated with a 0.1uf & 47uf Parallel capacitor 2. Tolerance: includes set up tolerance, line regulatino and load regulation

All specifications are typical at nominal input, full load, and 25°C unless otherwise noted

Astrodyne products are not authorized or warranteed for use as critical components in life support systems, equipment used in hazardous environments, nuclear controls systems, or other mission-critical applications.