AS320DRL 320 Watt DIN Rail Mount Switch Mode Power Supplies
|
AC input range selectable by switch |
|
|
Protections: Short circuit/Over load/Over voltage/Over Temperature |
|
|
Forced air cooling by built-in DC fan |
|
|
Cooling Fan ON-OFF auto control |
|
|
100% full load burn-in test |
|
|
Fixed switching frequency at 90KHz |
|
Model Number |
Output Voltage |
Output Amps |
Load Regulation |
Ripple and Noise |
Over Voltage Protection |
|
13.5V |
22A |
+/- 0.5% |
150mVp-p max. (Note 2) |
15.5 ~ 18.2v Hiccup mode, recovers automatically after fault condition is removed |
|
|
15V |
20A |
+/- 0.5% |
150mVp-p max. (Note 2) |
18 ~ 21v Hiccup mode, recovers automatically after fault condition is removed |
|
Model Number |
Over Temperature Protection |
Voltage Tolerance |
DC Voltage Adjust |
Minimum Load Requirement |
Efficiency |
|
RTH1 > 65°C fan on, < 55°C fan off, > 70°C (5 ~ 15v) Hiccup mode, recovers automatically after fault condition is removed |
+/- 1.0% (Note 3) |
12 ~ 15V |
0 ~ 22A |
83% typ. |
|
|
RTH1 > 65°C fan on, < 55°C fan off, > 70°C (5 ~ 15v) Hiccup mode, recovers automatically after fault condition is removed |
+/- 1.0% (Note 3) |
13.5 ~ 18V |
0 ~ 20A |
84% typ. |
|
|
RTH1 > 70°C fan on, < 65°C fan off, > 80°C (24 ~ 48v) Hiccup mode, recovers automatically after fault condition is removed |
+/- 1.0% (Note 3) |
26 ~ 32V |
0 ~ 11A |
86% typ. |
AS320/DRL series
|
Input Specifications
General Specifications
Environmental Specifications
|
Output Specifications
Physical Specifications
Notes 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 °C of ambient temperature. 2. Ripple and noise are measured at 20MHz of bandwidth by using a 12” twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Tolerance: includes set up tolerance, line regulation and load regulation. All specifications are typical at nominal input, full load, and 25°C unless otherwise noted Astrodyne products are not authorized or warranteed for use as critical components in life support systems, equipment used in hazardous environments, nuclear controls systems, or other mission-critical applications. |