Order by phone: 1-800-823-8082 / +1-508-964-6300 M-F 8:30am to 5:30pm EST

RS100 100w Switch Mode Power Supplies

100W Single Output Switching Power Supply

Universal AC input

Protections:Short circuit/Over load/Over voltage

Cooling by free air convection

LED indicator for power on

All using 105°C long life electrolytic capacitors

High efficiency, long life and high reliability

Model Number

Output Voltage

Output Amps

Load Regulation

Ripple and Noise

Over Voltage Protection

DC Voltage Adjust (typ.)

Efficiency

RS100-3.3

3.3 Volts(DC)

20 Amps

±2.0% (Note 4)

80mV pk-pk (Note 1)

3.8 ~ 4.45Volt(DC) Hiccup mode, auto recov

3.2~3.5Volt(DC)

0.74

RS100-5

5 Volts(DC)

16 Amps

±1.0% (Note 4)

80mV pk-pk (Note 1)

5.75 ~ 6.75Volt(DC) Hiccup mode, auto recov

4.75~5.5Volt(DC)

0.77

RS100-12

12 Volts(DC)

8.5 Amps

±0.5% (Note 4)

120mV pk-pk (Note 1)

13.8 ~ 16.2Volt(DC) Hiccup mode, auto recov

11.4~13.2Volt(DC)

0.81

RS100-15

15 Volts(DC)

7.0 Amps

±0.5% (Note 4)

120mV pk-pk (Note 1)

17.25 ~ 20.25Volt(DC) Hiccup mode, auto recov

14.25~16.5Volt(DC)

0.82

RS100-24

24 Volts(DC)

4.5 Amps

±0.5% (Note 4)

120mV pk-pk (Note 1)

27.6~ 32.4Volt(DC) Hiccup mode, auto recov

22.8~26.4Volt(DC)

0.84

RS100-48

48 Volts(DC)

2.3 Amps

±0.5% (Note 4)

200mV pk-pk (Note 1)

55.2~ 64.8Volt(DC) Hiccup mode, auto recov

45.6~52.8Volt(DC)

0.84

RS100 series

Input Specifications

Input Voltage Range

90 ~ 264 VAC; 125~373 Volts(DC)

Input Reflected Ripple Current

2.5 Amps. @ 115VAC, 1.5 Amps. @ 230VAC

Frequency Range

47-63 Hz

Inrush Current

40Amps / 230VAC (cold start)

General Specifications

Isolation

4242VDC

Isolation Input-Ground

2121VDC

Isolation Output-Ground

707VDC

Insulation Resistance

74%

Switching Frequency

UL60950-1, TUV EN60950-1 Approved

Environmental Specifications

Operating Temperature

-25°C to +70°C (See Derate Curve)

Storage Temperature

-40°C to +85°C, 10~95% RH

Relative Humidity

20~90% RH non cond

MTBF

260.8KHrs min,MIL-HDBK-217F(25°C)

EMS

Compliance to EN61000-4-2, 3, 4, 5, 6, 8, 11; ENV50204,EN61000-6-2(EN50082-2) heavy Industry Level, Criteria A

Output Specifications

Output Voltage

3.3 Volts(DC)

Output Amps

20 Amps

Load Regulation

±2.0% (Note 4)

Line Regulation

±0.5% (Note 3)

Temperature Coefficient

±0.03% / °C (0-50°C)

Ripple and Noise

80mV pk-pk (Note 1)

Over Voltage Protection

3.8 ~ 4.45Volt(DC) Hiccup mode, auto recov

Over Current Protection

110 ~ 150% rated output power Hiccup mode, auto recov

DC Voltage Adjust (typ.)

3.2~3.5Volt(DC)

Hold Up Time

100mS/230VAC, 18mS/115VAC

Size (mm)

159 x 97 x 38mm

Size (Inches)

6.26” x 3.81 ” x 1.50 ”

Weight (g)

600g

Weight (oz)

21.16oz

Notes

Physical Specifications

1. Ripple & noise are measured at 20MHz of bandwidth by using a 12” twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.

All specifications are typical at nominal input, full load, and 25°C unless otherwise noted

Astrodyne products are not authorized or warranteed for use as critical components in life support systems, equipment used in hazardous environments, nuclear controls systems, or other mission-critical applications.