Order by phone: 1-800-823-8082 / +1-508-964-6300 M-F 8:30am to 5:30pm EST

PWC Switch Mode Open Frame Power Supplies

PowerBlock Micro-Miniature 5 Watt Switching Power Supplies

5 Watts Output Power

3.3VDC to 24VDC Single Outputs

Universal Input

3,000VAC Input to Output Isolation

EN55022 Class B EMI

Industrial Op. Temp (“E” Versions)

Model Number

Output Voltage

Output Amps

Load Regulation

Line Regulation

Efficiency

PWC-3.3E

3.3 VDC

1.25 (Note 5)

±1%, max. (Note 6)

±1%, max. (Note 7)

65%

PWC-5E

5 VDC

1 (Note 5)

±1%, max. (Note 6)

±1%, max. (Note 7)

72%

PWC-12E

12 VDC

0.42 (Note 5)

±0.5%, max 20%--FL (Note 6)

±0.5% max (Note 7)

73%

PWC-15E

15 VDC

0.34 (Note 5)

±0.5%, max 20%--FL (Note 6)

±0.5% max (Note 7)

75%

PWC-24E

24 VDC

0.23 (Note 5)

±0.5%, max 20%--FL (Note 6)

±0.5% max (Note 7)

76%

PWC series

Input Specifications

Input Voltage Range

90-264VAC/110-340VDC Nominal: 100-240VAC

Frequency Range

47-440 Hz, 50-60Hz Nom.

Inrush Current

20A @ 115VAC, typ 40A@ 200VAC, typ

Environmental Specifications

Operating Temperature

-25 to +65°C FL See Derate Curves (Note 4)

Storage Temperature

-40 to +85°C

Relative Humidity

0-95%, Non-Condensing

EMI

EN55022

MTBF

790890 Hrs MIL-HDBK-217F, Notice 2, Parts Count

Physical Specifications

Size (Inches)

1 x 2 x 0.6

Construction

Encapsulated

Weight (g)

42g

Weight (oz)

1.5oz

Output Specifications

Output Voltage

3.3 VDC

Output Amps

1.25 (Note 5)

Load Regulation

±1%, max. (Note 6)

Line Regulation

±1%, max. (Note 7)

Preset Accuracy

±1%, typ (Note 8)

Temperature Coefficient

±0.03%/°C (0-50°C, typ.)

Ripple and Noise

150mV Pk-Pk, typ (Notes 1, 2 & 9)

Over Voltage Protection

Clamp

Over Temperature Protection

Latching, Recovering

Short Circuit Protection

Latching, Recovering

Hold Up Time

10mS, typ

General Specifications

Isolation

3000VAC (Note 3)

Isolation Input-Ground

2500VAC

Isolation Output-Ground

1000VAC

Efficiency

65%

Switching Frequency

132 Khz, fixed, typ

Safety Approvals

UL60950, EN60950

Notes

1. All measurements should be made directly at the terminals of the power supply

2. Ripple and noise dependent upon output voltage as specified per particular model.

3. Isolation for up to 1 minute duration. 4. Specified for free air convection cooling.

5. Minimum load is not required for proper peration.

6. Load Regulation is measured from 5% to Full Load.

7. Line Regulation measured from High Line to Low Line.

8. Preset Accuracy measured at nominal load, 120VAC input.

9. O/P Noise measured directly at the pins/terminals at nominal load, 0.1uF bypass and 47uF electrolytic, pk-pk @ 20MHz bandwidth.

10. 100% Production Tested

All specifications are typical at nominal input, full load, and 25°C unless otherwise noted

Astrodyne products are not authorized or warranteed for use as critical components in life support systems, equipment used in hazardous environments, nuclear controls systems, or other mission-critical applications.