Order by phone: 1-800-823-8082 / +1-508-964-6300 M-F 8:30am to 5:30pm EST

MPS30 30w Power Supplies

Universal AC input

Low leakage current ≤0.3mA

Protections: Short circuit / Overload / Over voltage / Over temperature

Fixed switching frequency at 100KHz

Low cost

High reliability

Model Number

Output Voltage

Output Amps

Minimum Load Requirement

Ripple and Noise

Over Voltage Protection

Efficiency

MPS30-5

5 Volts(DC)

5 Amps

0~5 Amps

80mV pk-pk

5.5~6.75Volts(DC) Hiccup mode, auto recover

72%

MPS30-12

12 Volts(DC)

2.5 Amps

0~2.5 Amps

120mV pk-pk

13.2~16.2Volts(DC) Hiccup mode, auto recover

75%

MPS30-15

15 Volts(DC)

2 Amps

0~2 Amps

150mV pk-pk

16.5~20.25Volts(DC) Hiccup mode, auto recover

76%

MPS30-24

24 Volts(DC)

1.2 Amps

0~1.2 Amps

240mV pk-pk

26.4~32.4Volts(DC) Hiccup mode, auto recover

77%

MPS30-27

27 Volts(DC)

1.1 Amps

0~1.1 Amps

240mV pk-pk

29.7~36.45Volts(DC) Hiccup mode, auto recover

78%

MPS30-48

48 Volts(DC)

0.6 Amps

0~0.6 Amps

240mV pk-pk

52.8~64.8Volts(DC) Hiccup mode, auto recover

78%

MPS30 series

Input Specifications

Input Voltage Range

90-264VAC / 120-370 Volts(DC)

Frequency Range

47-63 Hz

Inrush Current

30Amps @ 230VAC Input (cold start)

Input Current

0.8Amps max @ 115VAC 0.5Amps max @ 230VAC

Leakage Current

< 0.3mA / 230 VAC

Harmonic Input Current

Compliance to EN61000-3-2,-3

Operating Temperature

0.03% / °C (0-50°C)

Storage Temperature

-20°C to +85°C, 10~95% RH

Relative Humidity

20 to +90% RH non cond

EMI

Compliance to EN55011 (CISPR11) Class B

MTBF

366.7KHrs min, MIL-HDBK-217F(25°C)

Vibration

10~500Hz, 2G10min./1cycle, period for 60min. each along X, Y, Z axes

EMS

Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204, EN55024, EN60601-1-2, medical level, criteria A

General Specifications

Environmental Specifications

Isolation

4000VAC

Isolation Input-Ground

1500VAC

Isolation Output-Ground

Short

Insulation Resistance

≥ 100MΩ

Efficiency

72%

Safety Approvals

UL2601-1 TUV EN60601-1 IEC60601-1 approved

Output Specifications

Output Voltage

5 Volts(DC)

Output Amps

5 Amps

Minimum Load Requirement

0~5 Amps

Load Regulation

±2.0%: 5Volts(DC) 1%: 12~48Volts(DC)

Line Regulation

±1.0%: 5~12Volts(DC) ± 5%: 15~48Volts(DC)

Temperature Coefficient

0.03% / °C (0-50°C)

Ripple and Noise

80mV pk-pk

Voltage Tolerance

±3% (note 2)

Over Voltage Protection

5.5~6.75Volts(DC) Hiccup mode, auto recover

Over Current Protection

Above 105% rated output power Hiccup mode, auto recover

Over Temperature Protection

Tj 135°C typ. (U1) detect on main conrol IC, auto recover

Rise Time

500mS, 30mS/230VAC 500mS. 30mS/115VAC

Hold Up Time

70mS @ 230VAC 12mS @ 115VAC

Physical Specifications

Size (mm)

101.6 x 65.8 x 23.5 mm

Size (Inches)

4” x 2.59” x 0.93”

Weight (g)

160g

Weight (oz)

5.64oz

Notes

1. Ripple and Noise are measured at 20MHz of bandwidth by using a 12” twisted pair-wire terminated with a 0.1uf & 47 uf parallel capacitor.

2. Tolerance: includes set up tolerance, line regulation and load regulation.

All specifications are typical at nominal input, full load, and 25°C unless otherwise noted

Astrodyne products are not authorized or warranteed for use as critical components in life support systems, equipment used in hazardous environments, nuclear controls systems, or other mission-critical applications.