60W Single Output Industrial DIN Rail Power Supply
DR60 60w Power Supplies
|
Universal AC Input |
|
|
Protections: Short circuit/ over load / over voltage |
|
|
Cooling by free air convection |
|
|
Can be installed on DIN rail S-35/7.5 or 15 |
|
|
Isolation class 2 |
|
|
Model Number |
Output Voltage |
Output Amps |
Ripple and Noise |
Over Voltage Protection |
Voltage Tolerance |
DC Voltage Adjust |
Minimum Load Requirement |
Efficiency |
|
5 Volts(DC) |
6.5 Amps |
80mVpk-pk (Note 1) |
5.75~6.75V Shut down o/p voltage, re-power |
±2% 5Volts(DC) only (Note 2) |
4.75~5.5V |
0 ~ 6.5Amps |
76% |
|
|
12 Volts(DC) |
4.5 Amps |
120mVpk-pk (Note 1) |
13.8~16.2V Shut down o/p voltage, re-power |
±1% 12~24Volts(DC) (Note 2) |
11.1~13.2V |
0 ~ 4.5Amps |
82% |
|
|
15 Volts(DC) |
4 Amps |
120mVpk-pk (Note 1) |
17.25~20.25V Shut down o/p voltage, re-power |
±1% 12~24Volts(DC) (Note 2) |
13.5~16.5V |
0 ~ 4Amps |
83% |
|
|
24 Volts(DC) |
2.5 Amps |
150mVpk-pk (Note 1) |
27.6~32.4V Shut down o/p voltage, re-power |
±1% 12~24Volts(DC) (Note 2) |
21.6~26.4V |
0 ~ 2.5Amps |
84% |
DR-60 series
|
Input Specifications
General Specifications
Environmental Specifications
|
Output Specifications
Physical Specifications
Notes 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25°C of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwith by using a 12” twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. All specifications are typical at nominal input, full load, and 25°C unless otherwise noted Astrodyne products are not authorized or warranteed for use as critical components in life support systems, equipment used in hazardous environments, nuclear controls systems, or other mission-critical applications. |