DR45 45w Power Supplies

45W Single Output Industrial DIN Rail Power Supply

Universal AC input

Protections: Short circuit/Over load/Over voltage/Over Temperature

Cooling by free air convection

Can be installed on DIN rail S-35/7.5 or 15

Isolation class 2

LED indicator for power on. UL508 (industrial control equipment) approved

Model Number

Output Voltage

Output Amps

Ripple and Noise

Over Voltage Protection

Voltage Tolerance

DC Voltage Adjust

Minimum Load Requirement

Efficiency

DR-45-5

5 Volts(DC)

5 Amps

100mVpk-pk (Note 1)

5.75~6.75V Shut off o/p voltage, auto recover

±2%: 5Volts(DC) only (Note 2)

4.75~5.5V

0 ~ 5Amps

72%

DR-45-12

12 Volts(DC)

3.5 Amps

200mVpk-pk (Note 1)

13.8~16.2V Shut off o/p voltage, auto recover

±1%: 12~24Volts(DC) (Note 2)

10.8~13.2V

0 ~3. 5Amps

77%

DR-45-15

15 Volts(DC)

2.8 Amps

240mVpk-pk (Note 1)

17.25~20.25V Shut off o/p voltage, auto recover

±1%: 12~24Volts(DC) (Note 2)

13.5~16.5V

0 ~ 2.8Amps

77%

DR-45 -24

24 Volts(DC)

2 Amps

480Vpk-pk (Note 1)

27.6~32.4V Shut off o/p voltage, auto recover

±1%: 12~24Volts(DC) (Note 2)

21.6~26.4V

0 ~ 2Amps

80%

DR-45 series

Input Specifications

Input Voltage Range

90~264VAC / 120-370 Volts (DC)

Frequency Range

47 ~ 63Hz

Inrush Current

15 Amps @ 115VAC Input / 30 Amps @ 230VAC Input (Cold Start) typ.

Input Current

28 Amps. @ 115VAC / 56 Amps. @ 230VAC

Leakage Current

<1mA / 240VAC

General Specifications

Isolation

3000VAC

Isolation Input-Ground

1500VAC

Isolation Output-Ground

500VAC

Insulation Resistance

? 100M? @ 500VDC

Efficiency

72%

Safety Approvals

UL508 TUV EN60950-1 approved

Harmonic Current

Compliance to EN61000-3-2,-3

Environmental Specifications

Operating Temperature

-10°C to +50°C (See Derate Curve)

Storage Temperature

-40°C to +85°C

Working Humidity

20~90% RH non condensing

Storage Humidity

10 ~ 95% RH

EMI

Compliance to EN55011 EN55022B (CISPR22B)

MTBF

364.6K Hrs min,MIL-HDBK-217F(25°C )

Vibration

10~500Hz, 2G10min./1cycle, period for 60min. each along X, Y, Z axes Mounting: Compliance to IEC60068-2-6

EMS

Compliance to EN61000-4-2, 3, 4, 5, 6, 8, 11, ENV50204, EN55024, EN61000-6-2, EN61204-3,heavy industry level,criteria A

Output Specifications

Output Voltage

5 Volts(DC)

Output Amps

5 Amps

Load Regulation

± 1.0%

Line Regulation

±1% max

Temperature Coefficient

0.03%/°C (0 ~ 50°C)

Ripple and Noise

100mVpk-pk (Note 1)

Over Voltage Protection

5.75~6.75V Shut off o/p voltage, auto recover

Over Current Protection

105~160% rated output power Constant current limiting,auto recover

Over Temperature Protection

Tj 135 °C typ(U1)on heat sink of power transistor, Shut off o/p voltage, auto recover

Voltage Tolerance

±2%: 5Volts(DC) only (Note 2)

DC Voltage Adjust

4.75~5.5V

Minimum Load Requirement

0 ~ 5Amps

Rise Time

800ms, 60ms/230VAC @ FL

Hold Up Time

100mS @ 230VAC @ FL

Physical Specifications

Size (mm)

93 x 78 x 67

Size (Inches)

3.66” x 3.07 ” x 2.64 ”

Weight (g)

310g

Weight (oz)

10.93 oz

Notes

1. Ripple & Noise are measured at 20MHz of bandwidth by using a 12” twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.

2. Tolerance: includes set up tolerance , line regulation and load regulation.

All specifications are typical at nominal input, full load, and 25°C unless otherwise noted

Astrodyne products are not authorized or warranteed for use as critical components in life support systems, equipment used in hazardous environments, nuclear controls systems, or other mission-critical applications.